Nalazite se na CroRIS probnoj okolini. Ovdje evidentirani podaci neće biti pohranjeni u Informacijskom sustavu znanosti RH. Ako je ovo greška, CroRIS produkcijskoj okolini moguće je pristupi putem poveznice www.croris.hr
izvor podataka: crosbi !

The Feasibility Analysis of Replacing the Standard Ammonia Refrigeration Device with the Cascade NH3/CO2 Refrigeration Device in Food Industry (CROSBI ID 204219)

Prilog u časopisu | izvorni znanstveni rad | međunarodna recenzija

Jankovich, Dennis ; Osman, Krešimir The Feasibility Analysis of Replacing the Standard Ammonia Refrigeration Device with the Cascade NH3/CO2 Refrigeration Device in Food Industry // Thermal science, 19 (2015), 5; 1821-1833. doi: 10.2298/TSCI130611097J

Podaci o odgovornosti

Jankovich, Dennis ; Osman, Krešimir

engleski

The Feasibility Analysis of Replacing the Standard Ammonia Refrigeration Device with the Cascade NH3/CO2 Refrigeration Device in Food Industry

The thermodynamic analysis shows the feasibility of replacing the standard ammonia refrigeration device with the cascade NH3/CO2 refrigeration device in food industry. The main reason for replacing is to reduce the total amount of ammonia in spaces like deep-freezing chambers, daily chambers, working rooms and technical passageways. An ammonia-contaminated area is hazardous to human health and the safety of food products. This is why the preferred reduced amount of ammonia is accumulated in the Central Refrigeration Engine Room, where the cascade NH3/CO2 device is installed as well. Furthermore, the analysis discusses and compares two left Carnots refrigeration cycles, one for the standard ammonia device and the other for the cascade NH3/CO2 device. Both cycles are processes with two-stage compression and two-stage throttling. The thermodynamic analysis demonstrates that the selected refrigeration cycle is the most cost- effective process because it provides the best numerical values for total refrigeration factor for the observed refrigeration cycle ɛ. The main analyzed influential parameters of the cascade device are: total refrigeration load Q0, LC, total reactive power P, heat exchanger mean temperature Tm and condensing temperature of the low temperature part Tc, LC .

natural refrigerants; ammonia; carbon dioxide; ammonia refrigeration device; cascade NH3/CO2 refrigeration device; total refrigeration factor ɛ; total refrigeration load Q0; LC; total reactive power P; heat exchanger mean temperature Tm; condensing temperature of the low temperature part Tc; LC

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

Podaci o izdanju

19 (5)

2015.

1821-1833

objavljeno

0354-9836

10.2298/TSCI130611097J

Povezanost rada

Strojarstvo

Poveznice
Indeksiranost