Nalazite se na CroRIS probnoj okolini. Ovdje evidentirani podaci neće biti pohranjeni u Informacijskom sustavu znanosti RH. Ako je ovo greška, CroRIS produkcijskoj okolini moguće je pristupi putem poveznice www.croris.hr
izvor podataka: crosbi

Dynamic modeling approach for determining buildings technical system energy performance (CROSBI ID 231032)

Prilog u časopisu | izvorni znanstveni rad | međunarodna recenzija

Horvat, Ivan ; Dović, Damir Dynamic modeling approach for determining buildings technical system energy performance // Energy conversion and management, 125 (2016), 154-165. doi: 10.1016/j.enconman.2016.03.062

Podaci o odgovornosti

Horvat, Ivan ; Dović, Damir

engleski

Dynamic modeling approach for determining buildings technical system energy performance

This paper presents new approach for determining buildings technical system energy performance. This new methodology describes a mathematical model for accurately predicting indoor temperature and heat losses of the space heating and domestic hot water system components. The entire model is described by system of ordinary differential equations which can be solved using standard numerical techniques. The innovative aspect of the method is the integral approach in mathematical modeling of buildings energy needs and technical systems heat loss, taking into account heat accumulation in all considered parts (building envelope + technical system). Such approach allows a detailed insight of the system behavior for chosen working conditions. This model can serve for energy performance calculations in a wide variety of buildings types and their technical systems. The calculation example is given for family house, equipped with conventional space heating and domestic hot water heating system, with the time step of 1 min and for characteristic day of each month within a year. The results are compared against those obtain from EN ISO 13790 and standard series EN 15316. The comparison shows significant differences in determination of the annual delivered energy to the heating system (33%), as a consequence of difference in estimation of the energy need for heating (15%) and calculation of the technical systems recoverable heat losses utilization factor, which seems to be underestimated. The delivered energy to the space heating and domestic hot water heating system differs 25%, while the energy delivered to the generation system differs 4%.

Space heating system ; Domestic hot water system ; Dynamic simulation ; Building energy need ; Delivered energy

S.I.: Sustainable development of energy, water and environment systems for future energy technologies and concepts.

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

Podaci o izdanju

125

2016.

154-165

objavljeno

0196-8904

10.1016/j.enconman.2016.03.062

Povezanost rada

Strojarstvo

Poveznice
Indeksiranost