Analysis of the impact of different operating conditions on the performance of a reversible heat pump with domestic hot water production (CROSBI ID 244462)

Prilog u časopisu | izvorni znanstveni rad | međunarodna recenzija

Janković, Zvonimir ; Sierea Atienza, Jaime ; Cerdeira Perez, Fernando ; Pavković, Branimir Analysis of the impact of different operating conditions on the performance of a reversible heat pump with domestic hot water production // International journal of refrigeration-revue internationale du froid, 86 (2018), 282-291. doi: 10.1016/j.ijrefrig.2017.11.005

Podaci o odgovornosti

Janković, Zvonimir ; Sierea Atienza, Jaime ; Cerdeira Perez, Fernando ; Pavković, Branimir

engleski

Analysis of the impact of different operating conditions on the performance of a reversible heat pump with domestic hot water production

This paper presents the mathematical modelling of a liquid-to-water heat pump with scroll compressor, brazed plate heat exchangers, additionally built-in liquid-vapor heat exchanger (LVHX) and a desuperheater for domestic hot water (DHW) production. The refrigerant is the zeotropic mixture R407C and the liquid used in the outdoor loop is a propylene-glycol water mixture. Developed mathematical model is validated on experimental data and used as a tool for the heat pump analysis. Simulation results are obtained for the effect of the degree of superheat at the evaporator outlet, the subcooling degree at the condenser outlet, the effect of using or not the LVHX and the effect of using or not the desuperheater for DHW for typical operating conditions of liquid-to-water heat pumps (EN- 14511-2, 2011) in the cooling and heating modes (low and medium temperature applications). Results show that the effect of the degree of superheat or the decision on the suitability of using or not a LVHX may be different for heat pumps that include or not a desuperheater for DHW. In particular, if DHW is a priority, the use of a LVHX is recommended because it leads to higher COP (or EER) values as well as to higher DHW heating powers.

Heat pump ; Mathematical model ; Desuperheater ; Liquid-vapor heat exchanger ; Experimental results

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

nije evidentirano

Podaci o izdanju

86

2018.

282-291

objavljeno

0140-7007

1879-2081

10.1016/j.ijrefrig.2017.11.005

Povezanost rada

Strojarstvo

Poveznice
Indeksiranost